HomeMy WebLinkAboutPR 24488: PAEDC ACCEPTING A QUOTE FROM INDUSTRIAL AND COMMERCIAL MAINTENANCE (ICM) TO FURNISH AND INSTALL COMPRESSOR CONTACTORS AND FAN CONTRACTORS jN)RT*ARTH� � r L: R.
INTEROFFICE MEMORANDUM
Date: August 5, 2025
To: Honorable Mayor and City Council
Through: Ron Burton, CPM I City Manager
From: Krystle Muller I Interim CEO
RE: PR 24488 I The ratification of the PAEDC accepting a quote from Industrial and
Commercial Maintenance (ICM)to furnish and install 2 Circuits, 2 Compressors,
Compressor Contactors and 2 Fan Contractors to the Daikin Rooftop Unit at 501
Procter Street.
The intent of this Agenda Item is to seek the City of Port Arthur's City Council's ratification of the
PAEDC accepting a proposal from Industrial and Commercial Maintenance (ICM) to furnish and
install 2 Circuits, 2 Compressors, Compressor Contactors and 2 Fan Contractors to the Daikin
Rooftop Unit at 501 Procter Street.
Background:
ICM, an awarded vendor for Buyboard Contract #638-21; the PAEDC is contracted with them to
oversee the Preventative Maintenance of the HVAC system at 501 Procter Street. On July 21,2025,
ICM was called out to investigate/repair ongoing HVAC outages. Upon examination, it was
discovered that Circuit-2, Compressor-2 has bad wiring, Circuit-2, Compressor-1 has bad wiring,
and the fan contactors are worn and pitted causing the RTU main breaker to trip; PAEDC deemed
the need for emergency repairs for the public health, safety and welfare associated with occupancy
of the building.
Budgetary Impact:
The budgetary impact of this item is $21,903.92 funds available in PAEDC Account No. 120-80-
625-5318-00-00-000 (Equipment Maintenance).
Recommendation:
It is recommended that the City of Port Arthur's City Council ratifies the PAEDC's accepting a
proposal from Industrial and Commercial Maintenance (ICM) to furnish and install 2 Circuits, 2
Compressors, Compressor Contactors and 2 Fan Contractors to the Daikin Rooftop Unit at 501
Procter Street.
P.R. No. 24488
8/5/2025 JMC
RESOLUTION NO.
A RESOLUTION OF THE CITY COUNCIL OF THE CITY
OF PORT ARTHUR RATIFYING THE PORT ARTHUR
ECONOMIC DEVELOPMENT CORPORATION'S
ACCEPTANCE OF A PROPOSAL FROM INDUSTRIAL
AND COMMERCIAL MAINTENANCE (ICM) OF
BEAUMONT, TEXAS TO FURNISH AND INSTALL 2
CIRCUITS, 2 COMPRESSORS, COMPRESSOR
CONTACTORS, AND 2 FAN CONTACTORS FOR THE
HVAC UNIT AT 501 PROCTER STREET, AT A COST NOT
TO EXCEED $21,903.09, FUNDS AVAILABLE 120-80-625-
5318-00-00-000 (EQUIPMENT MAINTENANCE)
WHEREAS, the Port Arthur Economic Development Corporation ("PAEDC") owns the
property located at 501 Procter Street and is obligated to maintain this property; and
WHEREAS, Industrial and Commercial Maintenance ("ICM") is the vendor the PAEDC
is contracted with to oversee the Preventive Maintenance for the HVAC system at 501 Procter
Street; and
WHEREAS, on July 21, 2025, ICM was called out to investigate and repair ongoing
HVAC outages. Upon inspection, it was found that Circuit-2, Compressor-2, and Compressor-1
have defective wiring; the fan contactors are worn and pitted, resulting in the RTU main breaker
tripping; and
WHEREAS,pursuant to Section 252.022(a)(2) of the Texas Local Government Code,
the PAEDC has determined that repairs are necessary to preserve or protect the public health and
safety of the municipality's residents and occupancy of the building; and
WHEREAS, it is further authorized under Section 252.022(a)(3) due to unforeseen
damage to public machinery, equipment, or other property; and
WHEREAS, in accordance with Chapter 271 of the Texas Local Government Code, a
city may, through a resolution adopted by its governing body, participate in cooperative
purchasing programs such as Buyboard as an alternative to a formal bidding process; and
WHEREAS, ICM, an awarded vendor for Buyboard Contract #638-21, provided a
proposal for the necessary repair, Exhibit"A" in the amount of$21,903.09; and
WHEREAS, because of the immediate need to repair the HVAC system and the
PAEDC's obligation to maintain the property mentioned above, ICM has agreed to provide the
necessary repairs and will begin once the parts are received; and
WHEREAS, the PAEDC Board of Directors at their August 4, 2025 Board Meeting, has
ratified the acceptance of a proposal from Industrial and Commercial Maintenance in the same
form as the Proposal attached hereto as Exhibit"A".
NOW, THEREFORE, BE IT RESOLVED BY THE CITY COUNCIL OF THE
CITY OF PORT ARTHUR,TEXAS:
Section 1. That the facts and opinions in the preamble are true and correct.
Section 2. That the City Council hereby ratifies the Port Arthur Economic Development
Corporation to accept a proposal and performance from Industrial and Commercial Maintenance
to furnish and install 2 Circuits, 2 Compressors, Compressor Contactors, and 2 Fan Contractors.
Section 3. That a copy of the caption of this Resolution be spread upon the Minutes of
the City Council.
READ,ADOPTED AND APPROVED on this day of A.D., 2025,
at a Meeting of the City Council of the City of Port Arthur, Texas, by the following vote:
AYES:
Mayor
Councilmembers
•
NOES:
Page 2
Charlotte M. Moses,Mayor
ATTEST:
Sherri Bellard, City Secretary
APPROVED:
Krystl Muller,Interim PAEDC CEO
APPROVED AS TO FORM:
Charles E.Zech, PAEDC Attorney
APPROVED AS TO FORM:
Roxann Pais Cotroneo, City Attorney
APPROVED AS TO AVAILABILITY OF FUNDS:
Lynd Boswell, Fin nce Director
Page 3
EXHIBIT "A"
Page 4
CITY OF PORT ARTHUR ECONOMIC DEVELOPMENT COORPORATION—501 PROCTER ST.—ICM PROPOSAL TO
FURNISH AND INSTALL 2,CIRCUIT-2-COMPRESSORS,CONTACTORS,AND 2 FAN CONTACTORS
Industrial and Commercial
Mechanical
TACLA23943C
4445 Westpark Avenue
Beaumont,TX 77705
Phone(409)842-3737
Fax (409)842-3738
July 24,2025
PORT ARTHUR EDC
501 PROCTOR STREET BLDG.
PORT ARTHUR TX
ATTN: Mrs.Krystle Muller,CEO
Subject: EDC-501 PROCTER ST.—ICM PROPOSAL TO FURNISH AND INSTALL,2,CIRCUIT-2-
COMPRESSORS,COMPRESSOR CONTACTORS,AND 2 FAN CONTACTORS
DEAR MRS.VILLARREAL,MRS COLLAZO,MR.KHAN,
Industrial Commercial Mechanical is pleased to offer the following proposal to Furnish labor and materials to
perform the proposed repairs AS LISTED BELOW
Item QTY Description PRICE
1 1 Furnish qty of 1-TNT Crane-to lift Compressors and Job materials to rooftop Daikin AC Unit. $6476.31
2 2 qty of 2-Daikin pt no;113086904 Refrigerant Compressors $9558.86
2 1 qty of 1-misc.job service materials $230.77
3 2 qty of 2—25LB Drums of R410a Refrigerant $1033.85
4 1 qty of 1-Pt No 735028812 7/8"odf-Liquid line refrigerant Drier $38.46
5 4 qty of 4—Bottles;ACID AWAY Chemical Refrigerant Oil Treatment $246.15
6 2 qty of 2-Daikin Pt;349932321 Compressor Contact Relays 25A 3P 120VAC COIL $424.49
7 2 qty of 2—Daikin Pt;349932321 Cond Fan Contact Relays;25A 3P 120VAC COIL $213.14
8 1 qty of 1—Estimated Freight/Shipping Charges from Houston Texas. $461.54
ITEMS NOT INCLUDED IN PROPOSAL
1. Any changes or modifications not included in the proposal or proposed scope of work.
2. Warranty of any items not furnished and installed by ICM.
3. Charges for Original Diagnostic Service Call are not included in this Proposal.
ICM PRICE TO PERFORM THE PROPOSED WORK.
PARTS $18,863.09
LABOR $ 3,040.00
TOTAL $21,903.09-SALES TAX NOT INCLUDED
PLEASE ALLOW ESTIMATED 7-10 BUSINESS DAYS-FOR SHIPMENT OF PARTS.-AROPO
This Proposal is Valid for 30 days from the date proposal is furnish.
INDUSTRIAL&COMMERCIAL MECHANICAL IS AN AWARDED VENDOR FOR BUYBOARD CONTRACT#638-21
We would appreciate the opportunity to provide these services.Please let me know if you would like to proceed with
the proposed service repair,and what purchase order number we will utilize,for our billing for services.
As always,we thank you for your business and the opportunity to provide our services.
Regards,
Jerry F. Jofinson
ICM Sales Representative
I \( I.k 23943('- Regulated by the I eaas Department of Licensing and Regulation
PO Box 1215"'
ustin.'1 V
I-8011-8t13'202.512-463-6599
/°°11.°I.W1
' 3 Forest Circle
Call Summary Jurupa upa Valley CA 9175e
www.arcticomgroup.com
Customer Name Location Date
CITY OF PA-ECONOMIC DEVELOPMENT Pa Edc-Proctor Bldg 7/21/2025
Customer Address Location Address
501 Procter Street, Suite 100 501 Procter Street
Port Arthur,TX 77640 Port Arthur, TX 77640
Phone
(409)963-0579 x0000
Description Service Call ID P.O.#
CK RTU MAIN BREAKER TRIPPED 250721-0027 22504683
AG
Resolution
7/21/2025 Hoang, Stefan -0001
7-21 SH: Main package unit on the roof has several issues- Found circuit 2 compressor 2 has bad windings (weak
insulator)which read 1 Meg to ground which is high. Circuit 2 compressor 1 also has bad windings which read 22 Meg
which is also high. But we turn the#2 off so it won't trip the main breaker. We also found the fan contactors are worn and
pitted which cause the fan not to run sometimes. Washed the condenser coils.
Gave all information to Jerry for quote. This job is completed.
Labor
Technician Appointment Date Hours Description Completion Date
Stefan Hoang 0001 7/21/2025 8.00 7-21 SH REGULAR 7/21/2025
Thank You
Thank you for allowing us to assist you with your maintenance needs. We hope we have provided you with the
prompt and high quality service that you deserve. We hope you will sincerely consider ICM first for any future
maintenance demands.
Page 1 of 1